Wednesday, 12 March 2014
Case Study: Llwynderw Primary School
Llwynderw Primary School is a project in Abergaveny that MACH Acoustics worked on in partnership with Stride Treglown Architects and Willmott Dixon.
The school incorporates natural ventilation through a vented facade and openable windows, which cross ventilate classrooms via a central chimney - saving money, building space and simplifying the construction.
An important stage in the acoustic design of a building is an environmental noise survey of the existing site, a service provided by MACH Acoustics.
Using the data collected, a dynamic noise map was constructed and used to access the noise levels at each facade and the resulting noise break-in within the teaching spaces. It was clear that the site was not particularly noisy and that an open window would provide enough attenuation at the facade facing away from the roads - simple and low cost.
A ventilation strategy was developed in close coordination with Stride Treglown Architects - using the sound map - which efficiently attenuated noise on each facade.
On the noisy road facing facades, a cedar shingles feature created a duct, with intake perpendicular to the ground and containing the NVA. A 90deg arrangement like this increases attenuation and minimises impact on building space - highlighting the bespoke design options that the NVA offers. The quieter rooms with central chimney simply used openable acoustic windows.
The central chimney shown above is the highlight of the natural ventilation project. Each stack of classrooms featured a small square chimney, which vented out through natural vent towers on the roof of the building.
A testament to the NVAs versatility whilst maintaining class leading acoustic performance, the build was impressive architecturally whilst naturally ventilating and meeting both BB93 and BB101 requirements as a teaching space.
Thanks to a partnership between MACH Acoustics and Strides, the building received a BREEAM ‘Very Good’ rating and was well received by parents, pupils and residents of the area.
Click the preview below to download the full case study:
Wednesday, 26 February 2014
Case Study: Hertfordshire University
The Law Court at the University of Hertfordshire is a £10M
advanced facility, including a full-scale courtroom with public gallery, a
working law clinic, a purpose built mediation centre and a dedicated CPD suite,
as well as a large number of offices and classrooms. A BREEAM project, the
building was to be naturally ventilated. MEP designers AECOM specified the Mach Acoustics NatVent Attenuator to provide a vented facade solution using
weather louvres, connected to a raised, vented floor containing the Nat Vent
Attenuator.
![]() |
| Image provided by Aecom |
Due to the bespoke nature of the NVA, the attenuator could be simply installed in coordination with the modular grid based flooring. The NVA segments were slid into place between the pedestals (1/4 circle sections were added to the corner profile to account for the structure), followed by the matching 600x600mm floor sections. Building services often exist within the flooring void, including a heated element in this case. The NVA foam can be easily adapted on site to accommodate for these items, unlike a common pre-defined attenuators.
Click the preview below to download the full case study:
Wednesday, 19 February 2014
Case Study: Dartington Primary School Nat Vent Box
Dartington Primary School is located in close proximity to the A384; a large busy road. A number of natural ventilation strategies were developed in cooperation with Arup, including the use of landscaping as a barrier. This inspiring solid timber project presented challenges internally and externally. Natural ventilation is achieved through an external bulkhead cross-venting through the roof.
The first step of any noise break-in assessment is to establish levels across the site. This was done by carrying out noise monitoring throughout the site, over the full operational hours of the school.
A noise map was then created and used to assess the required level of attenuation required by facades of the school. The results indicated that the noise levels at the facades to the classroom block were higher than desirable.
The solution to the high noise levels at the building facade was to naturally ventilate using an external ground floor bulkhead containing the NVA, with hot air flowing out through openable window vents also containing the NVA. This solution allows for natural ventilation when it would otherwise not be possible through an open window for example.
In addition to this, an acoustic screen and a strategically placed earth bund were designed to reduce noise levels at the classroom facade. The bund was formed from recycled tires, adding to the sustainability credentials of the building.
Dartington Primary School is an inspiring development because a solid timber construction system has been used. BB93 also sets room reverberation requirements and the exposed timber in combination with barn shaped classrooms required some form of room acoustic treatments. The solution used was several acoustic beams provided by MACH Products (below).
The school met all BB93 requirements and BB101 ventilation specifications. Not only this but the finished design was pleasing and added function to the facade besides ventilation.
The build was featured in ‘BD Reviews’ sustainability issue, a bow to the innovative design by MACH Acoustics, White Design and Arup. The photo below features the wooden beams put in place to reduce the reverberation.
Click the preview below to download the full case study.
Thursday, 6 February 2014
Demonstration of Sound Level Difference through Window Opening
When testing the performance of the NAT Vent Attenuator at Winford Primary School, we performed a noise break in assessment whilst opening a window. The video above illustrates the sound level difference has a steep decay from a small opening.
Monday, 18 November 2013
Finite-Difference Time-Domain Models of Open Windows
An important area of research for MACH Acoustics, below are a few examples of a FDTD model we have produced to demonstrate various open window conditions.
First a top swung window, notice the noise ingress into the room.
The above but as a bottom swing.
An open window representation.
The above but with a internal baffle.
If you find this content interesting, why not arrange a CPD with MACH Acoustics?
First a top swung window, notice the noise ingress into the room.
The above but as a bottom swing.
An open window representation.
The above but with a internal baffle.
If you find this content interesting, why not arrange a CPD with MACH Acoustics?
Friday, 11 October 2013
Case Study - University of Hertfordshire Law Court
The Law Court at the University of Hertfordshire is a £10M building with advanced facilities, including a full-scale courtroom with public gallery, a working law clinic, a purpose built mediation centre and a dedicated CPD suite, as well as a large number of offices and classrooms. Aiming for BREEAM status, the building was to be naturally ventilated. MACH Acoustics provided a vented facade solution using weather louvres, connected to a raised, vented floor containing the NVA.
Situated on a busy campus and next to a busy bus route, the natural ventilation strategy need to be acoustically attenuated. Adding to the challenge was the fact that the building had already be designed for air inflow through the flooring, with acoustic dampers, louvre and bird mesh limiting flow to an already small 1.5m2 face area.
Only thanks to the adaptable NVA foam, MACH was able to design the attenuator around modulated Kingspan flooring, sitting on pedestals 360mm high, fully filling the void. The profile was designed to the same size as the 600x600mm grid created by the flooring, such that the NVA would be easy to install. By installing in segments like this, we were able to create the required length of attenuator for the noise level at the facade.
The vent openings are made within the spandrel panel between transoms. Air passes into the cellular space by passing through a external vent opening, through the NAT Vent Attenuator. The floor void is used as plenum - air enters the rooms above by means of floor diffusers.
Due to the bespoke nature of the NVA, the attenuator could be simply installed in coordination with the modular grid based flooring. The NVA segments were slid into place between the pedestals (1/4 circle sections were added to the corner profile to account for the structure), followed by the matching 600x600mm floor sections
Building services often exist within the flooring void, including a heated element in this case. The NVA foam can be easily adapted on site to accommodate for these items, unlike a common pre-defined attenuators.
The build meet the BB93 and BB101 requirements as a teaching space whilst creating a dynamic and pleasant space for students. MACH Acoustics and it’s partners helped the centre become one of the most innovative law schools in the UK and was recently awarded ‘The Most Sustainable Construction Award 2011’ by Building Futures and has been short listed for several other awards.
Click the preview below to download the complete case study (pdf)
Friday, 4 October 2013
Case Study - Llwynderw Primary School
The school incorporates natural ventilation through a vented facade and openable windows, which cross ventilate classrooms via a central chimney - saving money, building space and simplifying the construction.
An important stage in the acoustic design of a building is an environmental noise survey of the existing site, a service provided by MACH Acoustics.
Using the data collected, a dynamic noise map was constructed and used to access the noise levels at each facade and the resulting noise break-in within the teaching spaces. It was clear that the site was not particularly noisy and that an open window would provide enough attenuation at the facade facing away from the roads - simple and low cost.
A ventilation strategy was developed in close coordination with Stride Treglown Architects - using the sound map - which efficiently attenuated noise on each facade.
On the noisy road facing facades, a cedar shingles feature created a duct, with intake perpendicular to the ground and containing the NVA. A 90deg arrangement like this increases attenuation and minimises impact on building space - highlighting the bespoke design options that the NVA offers. The quieter rooms with central chimney simply used openable acoustic windows.
The central chimney shown above is the highlight of the natural ventilation project. Each stack of classrooms featured a small sqaure chimney, which vented out through natural vent towers on the roof of the building. Details of the this are shown on the right.
A testament to the NVAs versatility whilst maintaining class leading acoustic performance, the build was impressive architecturally whilst naturally ventilating and meeting both BB93 and BB101 requirements as a teaching space.
Thanks to a partnership between MACH Acoustics and Strides, the building received a BREEAM ‘Very Good’ rating and was well received by parents, pupils and residents of the area.
Click the preview below to download the full case study (pdf)
Thursday, 28 April 2011
Case Study - St Peter's Primary School Discrete Facade
St Peters school is located in relatively close proximity to the M5 and as such, environmental noise levels are too high to allow for natural ventilation through openable windows. MACH Acoustics was employed by South Gloucestershire Council to provide a range of design options to prevent noise ingress into this classroom.
One of the unique elements of this project was a considerable slope across the site. The solution was to pile the site and use suspended slabs to form the classrooms. To provide an external play/learning area to each of the classrooms, a suspended timber deck was employed. The solution here was to accommodate the attenuator within bench seating. Air was brought in from under the timber decking and then cross vented across the classroom before being released at high levels on the quiet side of the building.
Click the preview below to download the complete case study.
Case Study - London and West London Acadamies
London and West London Academies, two large £30M+ Academy are both designed around a natural ventilation, incorporating cross ventilation. Both schools were required to meet BB93 and BB101 ‘Ventilation of School Buildings’. MACH Acoustics worked with Fosters and Partners to develop a practical solution. Our findings were that the cost of conventional attenuators along with their size and short falls in performance prohibited the use of these devices but allowed for the NVA.
The academies featured many different imaginative implementations of the NVA as a cross ventilator, all venting into a central atrium. Air passed though the facade via actuated windows through bulkheads at ceiling height containing the NVA.
The main principle was to add an attenuator with 25% free area and a face area of 1.5m2, with small splitter sizes. The attenuator was to be located above a cupboard spaces as shown below. A flap enable the vent to be opened and closed.
One of the main advantages of the NVA is the ease and simplicity of installation. Once the bulkhead has been constructed, the tessellating foam is arranged into honeycomb pairs by alternating orientation, then simply slid into the duct. Since the foam is malleable and can be cut, fitting around building services or any on-site alternations can be easily achieved. Installation generally takes under one hour - saving money and construction time.
With the window facade bulkhead, we were able to implement cost savings by negating the need for expensive weather louvres, using actuated windows instead. Not only was the cost significantly reduced but the installation was greatly simplified - both points highly valued by the contractor.
With the window facade bulkhead, we were able to implement cost savings by negating the need for expensive weather louvres, using actuated windows instead. Not only was the cost significantly reduced but the installation was greatly simplified - both points highly valued by the contractor.
Click the preview below to download the complete case study
Case Study - Windford Primary School
Winford school is located directly under the flight path of Bristol Airport, as such noise ingress is a significant issue. During the design stage of this building several design options where reviewed.
The school is a prime example of the versatility of the NVA and MACH Acoustics. Facade ventilation is incorporated through window and horizontal louvres. Cross ventilation is applied through internal benches and exhausted through atrium vents.
For the design of this building cost was a primary factor. There was a desire to naturally ventilate but under the flight path of Bristol Airport and with cost limits it was a challenge acoustically.
A full natural ventilation strategy was designed in partnership with Stride Treglown Architects. Air would enter the building through openable windows and horizontal louvred ducts - controlled by a BMS - ventilate classrooms and exit through the roof of a central atrium known as the ‘heart’. Cross ventilators were designed between floors, discretely ducted within ground level benches - maximising building usage.
The central ‘heart’ of the building includes a plenum, where the hot air will exit the building. The design included a NVA bulkhead, mounted with BMS controlled actuated windows.
Working with Strides, the flexibility and bespoke nature of the NVA allowed for this design and enabled the same space to include solar thermal panels.
The school was fully compliant with BB93, confirming exceptional acoustic design considering the potential clash between natural ventilation and the busy Bristol Airport flight path.
Importantly, the reception of the building has been extremely positive, with teachers, parents and pupils heaping praise for the spacious and pleasant working environment. Winford’s pupils, who, according to parents are now ‘excited’ to go to school, enjoy day lit, naturally ventilated internal spaces with glazed screens between them so that all activity is in view.
The build received a BREEAM ‘Very Good’ rating and will generate a minimum of 15% of predicted energy consumption, thanks in part to the well executed natural ventilation system.
The school is a prime example of the versatility of the NVA and MACH Acoustics. Facade ventilation is incorporated through window and horizontal louvres. Cross ventilation is applied through internal benches and exhausted through atrium vents.
For the design of this building cost was a primary factor. There was a desire to naturally ventilate but under the flight path of Bristol Airport and with cost limits it was a challenge acoustically.
A full natural ventilation strategy was designed in partnership with Stride Treglown Architects. Air would enter the building through openable windows and horizontal louvred ducts - controlled by a BMS - ventilate classrooms and exit through the roof of a central atrium known as the ‘heart’. Cross ventilators were designed between floors, discretely ducted within ground level benches - maximising building usage.
The horizontal facade included thermal dampers, actuated by the building management system (BMS) and featured a 900 bend; reducing the protrusion and increasing acoustic attenuation.
Working with Strides, the flexibility and bespoke nature of the NVA allowed for this design and enabled the same space to include solar thermal panels.
The school was fully compliant with BB93, confirming exceptional acoustic design considering the potential clash between natural ventilation and the busy Bristol Airport flight path.
Importantly, the reception of the building has been extremely positive, with teachers, parents and pupils heaping praise for the spacious and pleasant working environment. Winford’s pupils, who, according to parents are now ‘excited’ to go to school, enjoy day lit, naturally ventilated internal spaces with glazed screens between them so that all activity is in view.
The build received a BREEAM ‘Very Good’ rating and will generate a minimum of 15% of predicted energy consumption, thanks in part to the well executed natural ventilation system.
Click the preview below to download the full case study (pdf).
Friday, 17 September 2010
Case Study - Dartington School Environmental Noise Break-in
Environmental noise break-in can be a significant issue when naturally ventilating a building located on a noise site, even if the noise is only moderate. Dartington school, previously reviewed within this blog with regard to the creative room acoustic treatment, also required creative forms of noise control measures to prevent noise break-in to noise sensitive teaching spaces.
The first stage of any noise break-in assessment is to establish noise levels across the site. This was done by carrying out noise monitoring throughout the site, over the full operational hours of the school. During the noise survey addition data was collect with respect to traffic flow levels and other data need to build a noise map of the site. A noise map was used such to assess the effects of the new school and to establish noise levels across all facades.
The result of the original noise mapping exercise is shown above in the left hand image. The results of this assessment indicated that noise levels at the facades to the classroom block where higher than desirable. The solution was to use an acoustic screen and strategically placed earth bund to reduce noise levels at the classroom. The tire wall is shown on the front cover of “BD Reviews” was used to form the required acoustics screen. This design is highly sustainable since these used tires did not go to land fill. Aesthetically there is a strong recycled image and additionally over time the vegetation shown in the image will cover the wall to form a green, live acoustics screen.
A second observation from the above noise mapping exercise was that noise levels at the sports hall were too high to allow for natural ventilation by means of simple openable vents. The solution was to added attenuated vents using the NAT Vent Attenuator. The photo below shows this vent and the diagram provides 3D view through the vent box.

The first stage of any noise break-in assessment is to establish noise levels across the site. This was done by carrying out noise monitoring throughout the site, over the full operational hours of the school. During the noise survey addition data was collect with respect to traffic flow levels and other data need to build a noise map of the site. A noise map was used such to assess the effects of the new school and to establish noise levels across all facades.
The result of the original noise mapping exercise is shown above in the left hand image. The results of this assessment indicated that noise levels at the facades to the classroom block where higher than desirable. The solution was to use an acoustic screen and strategically placed earth bund to reduce noise levels at the classroom. The tire wall is shown on the front cover of “BD Reviews” was used to form the required acoustics screen. This design is highly sustainable since these used tires did not go to land fill. Aesthetically there is a strong recycled image and additionally over time the vegetation shown in the image will cover the wall to form a green, live acoustics screen.
A second observation from the above noise mapping exercise was that noise levels at the sports hall were too high to allow for natural ventilation by means of simple openable vents. The solution was to added attenuated vents using the NAT Vent Attenuator. The photo below shows this vent and the diagram provides 3D view through the vent box.
Click the preview below to download the full case study on Dartington